THE THERMAL POTENTIAL OF AN EARTH TUBE HEAT EXCHANGER SYSTEM IN AIR TEMPERATURE MODERATING

Document Type : Original Article

Authors

1 Assistant prof. , Agric. Eng. Dept. Faculty of Agric, Kafrelsheikh University. Egypt.

2 Prof., Agric. Eng. Dept. Faculty of Agric, Kafrelsheikh University., Egypt.

3 Graduate Student, Agric. Eng. Dept. Faculty of Agric, Kafrelsheikh University. Egypt.

Abstract

The potential of earth tube heat exchangers in tempering ventilation air in delta region was studied experimentally by using two diffident systems. The two systems were installed at the research farm, faculty of agriculture, Kafrelsheikh University (31.07° N and 30.57° E), Kafrelsheikh governorate, Egypt. The first system (S1) consisted of one pipe with inner diameter of 10.85 cm. The second system (S2) consisted of two coaxial pipes the first pipe with inner diameter of 10.85 cm surrounded by the other one with inner diameter of 16.2 cm and the annular space between them filled by water and sealed. The length of both systems was 12 m and buried at a depth of 75 cm within two ditches 5 m apart and refilled with earth. The ambient air was blown by a 0.75 kW blower to pass through the two buried systems. The systems were operated during cooling and heating modes at four operating durations and five air velocities.  It was found that, the maximum temperature reduction and rise were 12.65 °C at air velocity 1.8 m/s, 12 hours operating duration and 6.27 °C at velocity 3.7 m/s, 12 hours operating duration under cooling and heating modes for S1 respectively.  Maximum thermal energy rate removed during cooling mode was 679.9 W for S2 at air velocity 9.7 m/s and 22 hours operating duration and the corresponding COP was 3.96. The maximum thermal energy rate added during heating mode was 629.7 W for S1 at air velocity 9.7 m/s, 12 hours operating duration and the corresponding COP was 3.67. Both systems contribute in air temperature control which declares in diminishing its amplitude. It was found that when the air velocity (mass flow rate) increase the thermal energy rate removed / added increases although the temperature reduction / rise decreases. This was because of the effect of increasing mass flow rate was predominant than the effect of temperature reduction/ rise in thermal energy rate exchanged evaluation.
Key words: Earth tube, thermal potential, earth to air heat exchanger

Main Subjects


Al-Ajmi, F. ; D.L. Lovedayb, and V.I. Hanbyc. 2006. The cooling potential of earth–air heat exchangersfor domestic buildings in a desert climate. Building and Environment 41 : 235–244.
Ascione, F.; L. Bellia and F. Minichiello. 2011. Earth-to-air heat exchangers for Italian climates. Renewable Energy 36 :  2177-2188.
Badescu, V. 2007. Simple and accurate model for the ground heat exchanger of a passive house. Renewable Energy 32 : 845–855.
Bansal, V. ; R. Misra, G. D. Agrawal, and J. Mathur. 2009. Performance analysis of earth–pipe–air heat exchanger for winter heating. Energy and Buildings 41 : 1151–1154.
Bansal, V. ; R. Misra, G. D. Agrawal, and J. Mathur. 2010. Performance analysis of earth–pipe–air heat exchanger for summer cooling. Energy and Buildings 42 : 645–648.
Darkwa, J.; G. Kokogiannakis, C.L. Magadzire, and K. Yuan. 2011. Theoretical and practical evaluation of an earth-tube (E-tube) ventilation system. Energy and Buildings 43 : 728–736.
Dubey.  H. ; B. kothi and K. Choudhary.  2016. Performance analysis of earth tube heat exchanger. International Journal of Engineering Science & Research Technology. (IJESRT), 5(7): 323-331.
Ghosal, M. K. ; and G. N. Tiwari. 2006 . Modeling and parametric studies for thermal performance of an earth to air heat exchanger integrated with a greenhouse. Energy Conversion and      Management  47 : 1779–1798.
Ghosal, M. K. ; G. N. Tiwari, and N. S. L. Srivastava. 2004 . Thermal modeling of a greenhouse with an integrated earth to air heat exchanger: an experimental validation. Energy and Buildings 36 : 219–227.
Kassem, A. M. M. 1999. Possibilities of using soil heat as renewable source for conditioning greenhouse. Ph.D. Thesis, Agric. Mech. Department, Faculty of Agriculture, Mansoura University.      
Lee, K. H. ; and R. K. Strand. 2008.  The cooling and heating potential of an earth tube system in buildings. Energy and Buildings 40 : 486–494.
Mihalakakou, G. 2003. On the heating potential of a single buried pipe using deterministic and intelligent techniques. Renewable Energy 28 : 917–927.
Mihalakakou, G.; M. Santamouris and D. Asimakopouris. 1994. On the cooling potential of earth to air heat exchangers. Energy Convers. Mgmt 35 (5) : 395-402.
Mongkon, S.; S. Thepa, P. Namprakai and N. Pratinthong. 2013. Cooling performance and condensation evaluation of horizontal earthtube system for the tropical greenhouse. Energy and Buildings 66 : 104–111.
Ozgener, O. and L. Ozgener. 2010 a. Exergetic assessment of EAHEs for building heating in Turkey: A greenhouse case study. Energy Policy 38 : 5141–5150.
Ozgener, L. and O. Ozgener. 2010 b. Energetic performance test of an underground air tunnel system for greenhouse heating. Energy 35 : 4079-4085.
Ozgener, O.; L. Ozgener and D. Y. Goswami. 2011. Experimental prediction of total thermal resistance of a closed loop EAHE for greenhouse cooling system. International Communications in Heat and Mass Transfer 38 : 711–716.
Pfafferott, J. 2003. Evaluation of earth-to-air heat exchangers with a standardized method to calculate  energy efficiency. Energy and Buildings 35:  971–983.
Vaz, J.; M. A. Sattler, E. D. dos Santos and L. A. Isoldi. 2011. Experimental and numerical analysis of an earth–air heat exchanger. Energy and Buildings 43 : 2476–2482.
Wu, H.; S. Wang and D. Zhu. 2007. Modelling and evaluation of cooling capacity of earth–air–pipe systems. Energy Conversion and Management  48 : 1462–1471.
Yoon, G.; H. Tanaka and M. Okumiya. 2009. Study on the design procedure for a multi-cool/heat tube system. Solar Energy 83 : 1415–1424.